1-10
Installation/Wiring
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
AC Input Phase Selection (Frames 5 & 6 Only)
Moving the “Line Type” jumper shown in
select single or three-phase operation. Remove plastic guard to access
jumper.
Important: When selecting single-phase operation, input power must be
applied to the R (L1) and S (L2) terminals only.
Cooling Fan Voltage
Common Bus drives require user supplied 120 or 240V AC to power the
cooling fans. The power source is connected between “0V AC” and the
terminal corresponding to your source voltage (see
Table 1.B Fan VA Rating
Selecting/Verifying Fan Voltage (Frames 5 & 6 Only)
Frames 5 & 6 utilize a transformer to match the input line voltage to the
internal fan voltage. If your line voltage is different than the voltage class
specified on the drive nameplate, it may be necessary to change the
transformer taps. The taps are shown in
!
ATTENTION: To avoid a shock hazard, ensure that all
power to the drive has been removed before performing
the following.
Frame
Fan Voltage(120V or 240V)
5
100 VA
6
138 VA
!
ATTENTION: To avoid a shock hazard, ensure that all
power to the drive has been removed before performing
the following: