D-6
HIM Overview
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
Numeric Keypad Shortcut
If using a HIM with a numeric keypad, press the ALT key and the +/– key to
access the parameter by typing its number.
Linking Parameters
Most parameter values are entered directly by the user. However, certain
parameters can be “linked,” so the value of one parameter becomes the
value of another. For Example: the value of an analog input can be linked to
[Accel Time 1]. Rather than entering an acceleration time directly (via
HIM), the link allows the value to change by varying the analog signal. This
can provide additional flexibility for advanced applications.
Each link has 2 components:
•
Source parameter – sender of information.
•
Destination parameter – receiver of information.
Most parameters can be a source of data for a link, except parameter values
that contain an integer representing an ENUM (text choice). These are not
allowed, since the integer is not actual data (it represents a value). Refer to
the list of parameters in
for information on which parameters can
be destinations. All links must be established between equal data types
(parameter value formatted in floating point can only source data to a
destination parameter value that is also floating point).
Establishing A Link
Step
Key(s)
Example Displays
1. Select a valid destination parameter to
be linked. The parameter value screen
displays.
2. Press Enter to edit the parameter. The
cursor will move to the value line.
3. Press ALT and then View (Sel). Next,
press the Up or Down Arrow to change
“Present Value” to “Define Link.” Press
Enter.
4. Enter the Source Parameter Number
and press Enter.
The linked parameter can now be
viewed two different ways by repeating
steps 1-4 and selecting “Present Value”
or “Define Link.” If an attempt is made to
edit the value of a linked parameter,
“Parameter is Linked!” will be displayed,
indicating that the value is coming from
a source parameter and can not be
edited.
5. To remove a link, repeat steps 1-5 and
change the source parameter number to
zero (0).
6. Press Esc to return to the group list.
Sel
Esc
or
ALT
+
Min: 0.01000
Max: 6553.5
Dflt: 10.0
Present Value
FG
P
: Parameter
Accel Time 1
Decel Time 1
S Curve Time
Parameter:
#32
Accel Time 1
Link:
800
Analog In1 Data
Define Link