Maintenance
Troubleshooting
Node Controller Hardware User Manual
117
Rockwell Automation Publication MMI-UM013B-EN-P - April 2020
Node Controller Troubleshooting
This section covers the determination of problems within the node controllers.
Table 6-3: Node Controller Related Troubleshooting
Symptom
Problem Description
Corrective Action
Node controller logs do not indi-
cate the correct time.
The battery for the clock in the
node controller has lost its charge.
Manually correct the time each
time the node controller is pow-
ered up or return the node control-
ler to MagneMotion for repair.
Use the node controller web inter-
face
Set Clock
function to set the
time (see the
Node Controller
Interface User Manual
).