Chapter 7
Diagnostic Status Indicators
Table 19 - Diagnostic Status Indicator Descriptions
Indicator
Status
Description and Recommended Actions
Module status
OFF
No power is applied to device.
AOP: ConnectionFaulted = 0
Check the voltage at terminals A1/A2.
Solid green
Device operating normally.
AOP: ConnectionFaulted = 0
No action necessary.
Flashing green
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Update module configuration (See
).
Check for missing IP address.
Check if automation controller is in program mode.
Cycle power.
Flashing red/green
Module self-test on power-up.
No action necessary.
Flashing red
Recoverable fault.
Complete firmware update.
Verify address switches.
Check for monitored safety relay fault - PWR/Fault indicator may be red or Device Fault bit may be 1.
Power was cycled to one of the monitored safety relays.
Cycle power.
Solid red
Unrecoverable fault; may require device replacement.
Cycle power.
Network status
OFF
Device is not online.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Flashing green
Device is online but has no CIP connections in the established state.
Solid green
Device online and has CIP connections in the established state.
Flashing red
One or more CIP connections in timed-out state.
Check for Guardmaster safety relay failure and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Link 1 or Link 2 Activity / Status
OFF
No link established. Check RJ45 connections at top or bottom of ENETR interface.
Solid green
One of the following conditions exists:
• A 100 Mbps (full or half-duplex) link exists.
• The ring network is operating normally.
No action necessary.
Flashing green
Transmit or receive activity present on indicated port @ 100 Mbps.
AOP: EthernetLinkxSts = 1 if ConnectionFaulted = 0
AOP: EthernetLinkxSts = 0 if ConnectionFaulted = 1.
No action necessary.
Solid yellow
One of the following conditions exists:
• A 10 Mbps (full or half-duplex) link exists.
• The ring network is operating normally.
• AOP: EthernetLinkxSts = 1 if ConnectionFaulted = 0.
• AOP: EthernetLinkxSts = 0 if ConnectionFaulted = 1.
No action necessary.
Flashing yellow
Transmit or receive activity present on indicated port @ 10 Mbps.
AOP: EthernetLinkxSts = 1 if ConnectionFaulted = 0.
AOP: EthernetLinkxSts = 0 if ConnectionFaulted = 1.
No action necessary.