Parameter Descriptions
3-39
Selects the drive’s response to increasing drive temperature and may reduce the
current limit value as well as the PWM frequency. If the drive is being used with a sine
wave filter, the filter is likely tuned to a specific carrier frequency. To ensure stable
operation, it is recommended that Drive OL Mode be set to 1 = Reduce CLim.
Sets the carrier frequency for the PWM output. Drive derating may occur at higher
carrier frequencies. For derating information, refer to Appendix A.
Important:
If Motor Cntl Sel (53) is set to FVC Vector, the drive will run at 2kHz
carrier frequency when operating below 6 Hz.
Selects amount of droop that the speed reference is reduced when at full load torque.
Zero disables the droop function.
Important:
Selecting “Slip Comp” with Feedback Select (80) in conjunction with
Droop RPM @ FLA may produce undesirable results.
150
Drive OL Mode
Range:
0 = Disabled
1 = Reduce CLim
2 = Reduce PWM
3 = Both-PWM 1st
Default:
3 = Both-PWM 1st
Access:
1
Path:
Dynamic Control>Load Limits
See also:
219
151
PWM Frequency
Range:
2 - 10kHz [2/4/8/10 kHz]
Default:
4 kHz
2 kHz (Frames 4-6, 575 VAC)
Access:
0
Path:
Dynamic Control>Load Limits
See also:
FV
152
Droop RPM @ FLA
Range:
0.0 to 200.0 RPM [0.1 RPM]
Default:
0.0 RPM
Access:
1
Path:
Dynamic Control>Load Limits
See also:
FV