Scales the upper value of the Speed Ref B Sel (93) selection when the source is an
analog input.
Scales the lower value of the Speed Ref B Sel (93) selection when the source is an
analog input.
Specifies the manual speed reference source when a digital input is configured for
auto/manual.
Important:
Analog ln 2 is not a valid selection if it was selected for Trim ln Select
(117), PI Feedback Sel (128), PI Reference Sel (126), Current Lmt Sel
(147) or Sleep Wake Ref (179).
Scales the upper value of the TB Man Ref Sel selection when the source is an analog
input.
94
Speed Ref B Hi
Range:
-/+Maximum Speed [0.1 Hz or 0.01 RPM]
Default:
Maximum Speed
Access:
1
Path:
Speed Command>Speed References
See also:
79, 93, 190
95
Speed Ref B Lo
Range:
-/+Maximum Speed [0.1 Hz or 0.01 RPM]
Default:
0.0
Access:
1
Path:
Speed Command>Speed References
See also:
79, 90, 93, 190
96
TB Man Ref Sel
Range:
1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level
Default:
2 = Analog In 2
Access:
1
Path:
Speed Command>Speed References
See also:
97, 98
97
TB Man Ref Hi
Range:
-/+Maximum Speed [0.1 Hz or 0.01 RPM]
Default:
Maximum Speed
Access:
1
Path:
Speed Command>Speed References
See also:
79, 96