3-150
DBT Reach Drive User Manual
Voltage used to compensate for long cables attached to inverter and motor. Identified
during autotune for Encoderless FVC.
Integral gain for current regulator for excitation of Flying start.
Proportional gain for current regulator for excitation of Flying start.
Input phase loss detection (level).
542
Encdlss Vlt Comp
Range:
0 to 115 [1]
Default:
6.1
Access:
2
Path:
Utility>Diag-Vector Cnt
See also:
543
Excitation Ki
Range:
0 to 32767 [1]
Default:
44
Access:
2
Path:
Utility>Diag-Vector Cnt
See also:
544
Excitation Kp
Range:
0 to 32767 [1]
Default:
1800
Access:
2
Path:
Utility>Diag-Vector Cnt
See also:
545
ln Phaseloss Lvl
Range:
10 to 1000 [1]
Default:
325
Access:
2
Path:
Utility>Diag-Vector Cnt
See also: