Chapter 4 Troubleshooting
Recovery Mode
The TotalFORCE control platform has a recovery mode. Recovery mode
recreates the product file system and all parameter data is defaulted. Use the
following procedure if the processor fails to start up.
Recovery Mode Procedure
1. Power down the product.
2. Locate the three IP address Switches on the main control board.
3. Record the positions of the switches so they can be set back to these
positions at the end of the procedure.
4. Set all three switches to position 8, for an overall value of 888.
5. Power up the product.
6. Wait for the STS indicator to turn flashing red and the ENET indicator to
turn steady red.
7. Power down the product.
8. Set the tens position switch to position 9 and the ones position switch to
position 7, for an overall value of 897.
9. Power up the product.
10. Wait for the STS indicator to turn flashing red and ENET indicator to
turn steady red.
11. Power down the product.
12. Set the IP address switches to the positions recorded in step 3.
13. Power up the product.