Chapter 3
Component Test Procedures
Check the AFE Power
Structure Fan Inverter Fuses
To check the AFE power structure fan inverter fuse, follow these steps.
1. Remove power from the AFE.
Remove Power from the AFE on page 37
.
2. If present, remove the protective barriers.
Remove AFE Protective Barriers on page 44
.
3. Remove the protective front covers and terminal covers from the power
structure for each phase (U, V, and W).
See
Remove Protective Covers from the Power Structure on page 47
.
4. A pair of fuses (F1 and F2) feed DC bus power to each fan inverter.
a. Locate these fuses (shown below) and remove them.
b. Use a multi-meter to verify that the fuses are not open.
5. Reinstall the good fuses and replace any open fuse with an equivalent-
rated fuse.