116
Rockwell Automation Publication 7000L-UM301F-EN-P - March 2020
Chapter 3
Operator Interface
Note
: The characters entered may only be valid for the currently selected
language. Any characters used which are unique for a given language (i.e. other
than the four sets defined above) can only be meaningfully displayed in the
selected language, because other languages do not contain the appropriate display
characters.
Configure the Drive
In order to tailor the drive to your motor and application, a number of elements
must be defined in the drive. The section describes how you will set or 'configure'
these elements of the drive, via this operator interface. You will learn how to:
•
Change a parameter setting.
•
Assign a parameter to an Analog Port.
•
Selectively enable or disable (i.e. Mask) certain faults.
•
Define your own faults attached to external inputs.
•
Configure the XIO
•
Define the information sent to your optional PLC connection.
•
Save and Restore your settings in the drive.
•
Select an alternate language (if previously loaded in operator interface)
There are two methods to configure the drive. This section defines the more
complete method to configure the drive for any application. The drive may also
be configured for the majority of applications by using the Setup Wizard. The
Setup Wizard can be entered from the "SETUP" screen by selecting the 'Setup
Wizard' from the list of options and pressing [enter].
Regardless of the method used for configuration, the default factory parameters
will be obtained from the Drive Identity Module (DIM). The use of the DIM
allows each drive to be customized at the factory to the intended application,
using all known information at the time of building the drive.
Enter/Modify an Access Level
The drive is protected from unauthorized changes via passwords consisting of a
number between 0....65,535. These passwords are associated with Access Levels.
Each Access Level, (except for the first one 'Monitor') has its own password
number (PIN). These values can be unique or all can be set to the same value.
The default level, 'Monitor' does not have a PIN associated with it. With this
Access Level, the drive configuration can be viewed, but no changes are allowed
to the parameters. In addition to providing the protection, the Access Levels also
filter out the amount of information that can be viewed at each level. On any
level, other than 'Monitor', any information that can be viewed may also be
modified.