Programming and Parameters
3-7
Monitor File
Fil
e
Gr
ou
p
No.
Parameter Name & Description
See
for symbol descriptions
Values
Relate
d
MONIT
O
R
Metering
001
[Output Freq]
Output frequency present at T1, T2 & T3
(U, V & W)
Default:
Min/Max:
Units:
Read Only
–/+[Maximum Freq]
0.1 Hz
002
[Commanded Speed]
Value of the active Speed/Frequency
Reference. Displayed in Hz or RPM,
depending on value of [Speed Units].
Default:
Min/Max:
Units:
Read Only
–/+[Maximum Speed]
0.1 Hz
0.1 RPM
003
[Output Current]
The total output current present at T1, T2
& T3 (U, V & W).
Default:
Min/Max:
Units:
Read Only
0.0/Drive Rated Amps
×
2
0.1 Amps
004
[Torque Current]
Based on the motor, the amount of
current that is in phase with the
fundamental voltage component.
Default:
Min/Max:
Units:
Read Only
Drive Rating
×
–2/+2
0.1 Amps
005
[Flux Current]
Amount of current that is out of phase
with the fundamental voltage component.
Default:
Min/Max:
Units:
Read Only
Drive Rating
×
–2/+2
0.1 Amps
006
[Output Voltage]
Output voltage present at terminals T1,
T2 & T3 (U, V & W).
Default:
Min/Max:
Units:
Read Only
0.0/Drive Rated Volts
0.1 VAC
007
[Output Power]
Output power present at T1, T2 & T3 (U,
V & W).
Default:
Min/Max:
Units:
Read Only
0.0/Drive Rated kW
×
2
0.1 kW
008
[Output Powr Fctr]
Output power factor.
Default:
Min/Max:
Units:
Read Only
0.00/1.00
0.01
009
[Elapsed MWh]
Accumulated output energy of the drive.
Default:
Min/Max:
Units:
Read Only
0.0/214748352.0 MWh
0.1 MWh
010
[Elapsed Run Time]
Accumulated time drive is outputting
power.
Default:
Min/Max:
Units:
Read Only
0.0/214748352.0 Hrs
0.1 Hrs
011
[MOP Reference]
Value of the signal at MOP (Motor
Operated Potentiometer).
Default:
Min/Max:
Units:
Read Only
–/+[Maximum Speed]
0.1 Hz
0.1 RPM
012
[DC Bus Voltage]
Present DC bus voltage level.
Default:
Min/Max:
Units:
Read Only
0.0/Based on Drive Rating
0.1 VDC
013
[DC Bus Memory]
6 minute average of DC bus voltage level.
Default:
Min/Max:
Units:
Read Only
0.0/Based on Drive Rating
0.1 VDC
Summary of Contents for Allen-Bradley PowerFlex 700 B Series
Page 10: ...P 6 Overview Notes ...
Page 36: ...1 26 Installation Wiring Notes ...
Page 118: ...3 78 Programming and Parameters Notes ...
Page 162: ...A 28 Supplemental Drive Information Notes ...
Page 227: ......