Rockwell Automation Publication 6000-IN100B-EN-P - October 2020
61
Appendix
C
General Wire Categories
General Wire Categories
Conductors Category
Voltage Class
Signal Examples
Recommended Cable
Conductors Group Notes
Customers Control Power <240V AC
120 or 220V, 1Ø
Per IEC / NEC, Local
codes and application
requirements
Tray or Conduit
Should only be run with 120 or 240 digital
control
Digital I/O
<240V AC
Dry Contact Relay Logic
Outputs
Per IEC / NEC, Local
codes and application
requirements
Tray or Conduit
Should only be run with Control Power
24V DC
POD I/O or Dry Contact Relay
Logic Output
Per IEC / NEC, Local
codes and application
requirements
Tray or Conduit
Can be run with Small Signal
Small Signal
Analog Signals
4…20 mA, ±10V
Belden 8760
(1)
Belden 8770
(2)
Belden 9460
(3)
Tray or Conduit
Can be run with 24V DC digital I/O
Communications
Ethernet, Internal Drive Link
(4)
CAT 5E
Tray or Conduit
(1)
18 AWG, twisted-pair, shielded
(2) 18 AWG, 3 conductor, shielded
(3) 18 AWG, twisted-pair, shielded
(4) Internal Drive Link Communication — The recommended cable to use is AB 1485C-P1C
xxx
, where
xxx
is the length of the cable on the spool (Belden type YR 39660).