t086 [EM Brk Off Delay]
Related Parameter(s):
Sets the time the drive remains at minimum frequency before ramping up to the commanded frequency (and engaging the brake coil relay) if Electromechanical (EM)
Brake Control Mode is enabled with
[Stop Mode].
Values
Default:
2.00 s
Min/Max:
0.00/10.00 s
Display:
0.01 s
Frequency
Time
[Minimum Freq]
[EM Brk Off Delay]
[EM Brk On Delay]
Stop
commanded
Start
commanded
EM Brk
de-energized (On)
Drive stops
EM Brk
energized (Off)
Ramp accel
Ramp decel
t087 [EM Brk On Delay]
Related Parameter(s):
Sets the time the drive remains at minimum frequency (after releasing the brake coil relay) before stopping if EM Brake Control Mode is enabled with
[Stop Mode].
Values
Default:
2.00 s
Min/Max:
0.00/10.00 s
Display:
0.01 s
Frequency
Time
[Minimum Freq]
[EM Brk Off Delay]
[EM Brk On Delay]
Stop
commanded
Start
commanded
EM Brk
de-energized (On)
Drive stops
EM Brk
energized (Off)
Ramp accel
Ramp decel
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...