94
Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Values
Default:
Relay Out1 Sel:
Relay Out2 Sel:
0
2
Min/Max:
0/31
Display:
1
Programmable Relay Outputs (Continued)
t077 [Relay Out1 Level]
Related Parameter(s):
t082 [Relay Out2 Level]
PowerFlex 525 only.
32 bit parameter.
Determines the on/off point for the output relay when
[Relay Outx Sel] is set to the values shown below.
Values
Default:
0.0
Min/Max:
0.0/9999.0
Display:
0.1
PF 525
3
2
Min/Max Value Range Based On [Relay Outx Sel] Setting
6:
0...500 Hz
10:
0...100%
16:
0.1...9999 s
20: 0/1
7:
0...180%
11:
0/1
17:
1...9999 counts
26: 0...150%
8:
0...815V
13:
0...800
18:
0...180 °C
–
t078 [RelayOut1 LevelF]
t083 [RelayOut2 LevelF]
PowerFlex 525 only.
Determines the on/off point (fractional portion) for the output relay.
Values
Default:
Read Only
Min/Max:
0.0/0.9 s
Display:
0.1 s
PF 525
t079 [Relay 1 On Time]
t084 [Relay 2 On Time]
PowerFlex 525 only.
Sets the delay time before Relay energizes after required condition is met.
Values
Default:
0.0 s
Min/Max:
0.0/600.0 s
Display:
0.1 s
PF 525
t080 [Relay 1 Off Time]
t085 [Relay 2 Off Time]
PowerFlex 525 only.
Sets the delay time before Relay de-energizes after required condition ceases.
Values
Default:
0.0 s
Min/Max:
0.0/600.0 s
Display:
0.1 s
PF 525
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...