Chapter 3 Programming and Parameters
Values
Default:
Opto Out1 Sel:
Opto Out2 Sel:
2
1
Min/Max:
0/31
Display:
1
Programmable Digital Outputs (Continued)
t070 [Opto Out1 Level]
t073 [Opto Out2 Level]
32 bit parameter.
PowerFlex 525 only.
Determines the on/off point for the digital outputs when
[Opto Outx Sel] is set to the values shown below.
Values
Default:
0.0
Min/Max:
0.0/9999.0
Display:
0.1
3
2
PF 525
Min/Max Value Range Based On [Opto Outx Sel] Setting
6: 0...500 Hz
10: 0...100%
16: 0.1...9999 s
20
:
0/1
7: 0...180%
11 0/1
17: 1...9999
counts
26
:
0...150%
8: 0...815V
13 0...800
18: 0...180°
–
t071 [Opto Out1 LevelF]
t074 [Opto Out2 LevelF]
PowerFlex 525 only.
Determines the on/off point (fractional portion) for the digital outputs.
Values
Default:
Read Only
Min/Max:
0.0/0.9 s
Display:
0.1 s
PF 525
t075 [Opto Out Logic]
PowerFlex 525 only.
Determines the logic (Normally Open/NO or Normally Closed/NC) of the digital outputs only.
Values
Default:
0
Min/Max:
0/3
Display:
1
PF 525
Setting Digital Out 1 Logic
Digital Out 2 Logic
0
NO
NO
1
NC
NO
2
NO
NC
3
NC
NC
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...