Rockwell Automation Publication 520-UM001K-EN-E - August 2021
231
Appendix F PID Set Up
PID Reference and
Feedback
PID mode is enabled by setting
[Speed Referencex] to
11 “PID1 Output” or 12 “PID2 Output”, and activating the corresponding speed
reference.
If
[PID x Ref Sel] is not set to 0 “PID Setpoint”, PID can still be
disabled by select programmable digital input options (parameters
,
...
[DigIn TermBlk xx]) such as “Purge”.
and
[PID x Fdback Sel] are used to select the source of the PID
feedback.
IMPORTANT
PowerFlex 523 has one PID control loop.
PowerFlex 525 has two PID control loops, of which only one can be in
use at any time.
A459, A471 [PID x Ref Sel] Options
Options
Description
0“PID Setpoint“
A464 or A476 [PID x Setpoint] will be used to set the value of the PID Reference.
1“Drive Pot”
The drive potentiometer will be used to set the value of the PID Reference.
2“Keypad Freq”
The drive keypad will be used to set the value of the PID Reference.
2”Serial/DSI”
The reference word from the Serial/DSI communication network becomes the PID Reference.
4“Network Opt”
The reference word from a communication network option becomes the PID Reference.
5“0-10V Input”
Selects the 0…10V Input. The PID will not function with a bipolar analog input. It will ignore any
negative voltages and treat them like a zero.
6“4-20mA Input”
Selects the 4…20 mA Input.
7“Preset Freq”
A410...A425 [Preset Freq x] will be used as an input for the PID Reference.
8“AnlgIn Multi”
(1)
(1) Setting is specific to PowerFlex 525 drives only.
The product of the 0…10V and 4…20mA Inputs will be used as an input for the PID Reference.
9“MOP Freq”
A427 [MOP Freq] will be used as an input for the PID Reference.
10”Pulse Input”
Pulse train will be used as an input for the PID Reference.
11“Step Logic”
(1)
Step Logic will be used as an input for the PID Reference.
12“Encoder”
(1)
Encoder will be used as an input for the PID Reference.
13“EtherNet/IP”
(1)
The reference word from the EtherNet/IP communication network becomes the PID Reference.
A460, A472 [PID x Fdback Sel] Options
Options
Description
0“0-10V Input”
Selects the 0…10V Input (default setting). The PID will not function with a bipolar analog input.
It will ignore any negative voltages and treat them like a zero.
1“4-20mA Input“
Selects the 4…20 mA Input.
2“Serial/DSI”
Serial/DSI will be used as an input for the PID Feedback.
3“Network Opt”
The reference word from a communication network option becomes the PID Reference.
4“Pulse Input”
Pulse train will be used as an input for the PID Feedback.
5“Encoder”
(1)
(1) Setting is specific to PowerFlex 525 drives only.
Encoder will be used as an input for the PID Feedback.
6“EtherNet/IP”
(1)
EtherNet/IP will be used as an input for the PID Feedback.
Summary of Contents for Allen-Bradley PowerFlex 520 Series
Page 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Page 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Page 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Page 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...