Rockwell Automation Publication 20P-TG003B-EN-P - September 2021
95
Access Procedures
Chapter 3
Remove the Bus Bars from a Regenerative Drive
8.
Remove the six bolts and washers that secure the intermediate bus bars to
the U and W phase AC input and DC output (terminals C and D) bus
bars. Note the size and location of the bolts and the order in which the
washers are placed on the bolts.
Remove bolts
and washers
Remove bolts
and washers
Nut
Lock washer
Flat washer
Flat washer
Bolt (30mm long)
Bolt (30mm long)
Flat washer
Flat washer
Lock washer
Nut
Left to right, two (2) bolts (40mm
long) and flat washers
Left to right, two (2)
nuts, lock washers
and flat washers
Left to right, two (2) flat
washers, lock washers
and nuts
Bolt Size and Washer Order
Left to right, two (2) flat
washers and bolts
(40mm long)