![Rockwell Automation Allen-Bradley PowerFlex 20P Manual Download Page 81](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-powerflex-20p/allen-bradley-powerflex-20p_manual_1475484081.webp)
Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
81
Access Procedures
Chapter 3
6.
Using a 12.5 mm (0.5 in.) socket wrench, loosen the four nuts (two at each
side) that secure the fan assembly bracket to the drive frame. To clear the
fan blower inlet, lift the fan assembly bracket up and remove the bracket
and fan assembly from the drive.
Install the Series A Fan Assembly
Install the series A fan assembly in the reverse order of removal. See the Series A
Fan Circuit Diagram on page
Secure the fan power wires using cable ties, as previously installed, to make sure
that the wires do not make contact with moving parts.
ATTENTION:
The edges of the blades on the fan blower may be sharp.
Take precautions to protect against personal injury when handling the
fan assembly.
6
6
Tightening torque:
18.0 N
•
m (159.3 lb
•
in)