Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
71
Access Procedures
Chapter 3
5. Disconnect the cables from connector XFCD and X3 on the field board.
6. Remove the 11 hexalobular screws that secure the field board to the
control EMI shield and remove the board.
Install the Field Circuit Board
Install the field circuit board in the reverse order of removal.
•
Inspect the cables that connect to connectors XFCD and X3 on the field
board for burn marks, cracks, or a loose connector. If necessary, replace the
existing cables with the new cables provided.
IMPORTANT
Mark all connections and wires before removal to avoid incorrect
wiring during reassembly.
XFCD
X3
1
TA_1
P F C - X X
R1
R4
C4
C7
Note: Field board for 70 A field supply shown.
T25
Tightening torque:
2.5…4.0 N
•
m
(22…35 lb
•
in)
Tightening torque:
1.0…1.2 N
•
m
(9…10.5 lb
•
in)
T25