Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
Chapter 3
Access Procedures
5.
Disconnect the cables from connector XA and XUV on the switching
power supply board.
6.
Remove the five screws that secure the board to the control EMI shield
and remove the board.
Install the Switching Power Supply Circuit Board
Install the switching power supply circuit board in the reverse order of removal.
•
Inspect the 16 Pin cable that connects to connector XA on the switching
power supply board for burn marks, cracks or a loose connector. If
necessary, replace the existing cable with the new cable provided.
Pulse Transformer Circuit
Board Removal and
Installation
Remove the Pulse Transformer Circuit Board
1.
Read the General Safety Precautions on page
2.
Remove power from the drive. See Remove Power from the Drive on page
3.
Remove the top control panel, bottom control panel, and I/O and control
terminal covers from the drive. See Remove the Protective Covers on page
XA
1
2
15
16
XSW
1
4
XSW1
1
4
XV
F1
1C2
1D2
XUV
1
6
T15
Tightening torque:
1.0…1.2 N
•
m
(9…10.5 lb
•
in)
5
6