Chapter 2
Component Test Procedures
Save the Parameter
Configuration
It is recommended that you save the drive and communication adapter parameter
configuration to a HIM set or by up loading the drive and adapter parameters to
an offline node file using Connected Components Workbench™ or
DriveExecutive™ software before performing any service or testing on the drive.
HIM sets are files stored in permanent nonvolatile HIM memory.
Save to a HIM Set
Follow these steps to save the drive and communication adapter parameters to a
HIM set.
1.
On the HIM, access the
Memory Storage
menu.
2.
Select the
HIM CopyCat
menu and press
.
3.
Select
Device
->
HIM
and press
.
4.
Do one of the following:
•
If there are no existing HIM sets, enter a name using the
and
buttons to select the desired characters and press
.
•
If there is an existing HIM set, press
to overwrite it, or select
No
using the
button and use the
and
buttons to select
the desired characters. Then press
.
The HIM set will be saved to nonvolatile memory.