Publication 2711P-UM001D-EN-P - September 2005
2-8
Installation
Mount the 700-1500
Terminal in a Panel
Mounting clips secure the terminal to the panel. The number of clips
you use (4, 6 or 8) varies by terminal type.
1.
Cut an opening in the panel using the panel cutout shipped with
the terminal.
2.
Make sure the terminal sealing gasket is properly positioned on
the terminal.
This gasket forms a compression type seal. Do not use sealing
compounds.
3.
If using keypad legend strips on keypad terminals, we
recommend that you install the strips before installing the
terminal.
Be careful not to pinch the legend strip during installation.
4.
Place the terminal in the panel cutout.
ATTENTION
•
Disconnect all electrical power from the panel
before making the panel cutout.
•
Make sure the area around the panel cutout is
clear.
•
Take precautions so metal cuttings do not enter
any components already installed in the panel.
•
Failure to follow these warnings may result in
personal injury or damage to panel components.
Sealing Gasket
Summary of Contents for Allen-Bradley PanelView Plus 400
Page 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Page 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Page 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Page 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Page 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Page 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Page 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Page 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Page 192: ......