Chapter 9
Parameter Descriptions
•
Process trim
, which takes the output of the PI regulator and sums it with a
master speed reference to control the process.
•
Process control
, which takes the output of the PI regulator as the speed
command. No master speed reference exists, and the PI output directly
controls the drive output.
Note that Speed Mode (80) must be set to Process PI (2).
Figure 41 - PI Control (125)
Bit 0 - PI Enable
• Enables/disables the operation of the PI loop.
Bit 1 - PI Hold
• Enabled = The integrator for the outer control loop is held at the
current level; that is, it will not increase.
• Enabled = The integrator for the outer PI control loop is allowed to
increase.
Bit 2 - PI Reset
• Enabled = The integrator for the outer PI control loop is reset to zero.
• Disabled = The integrator for the outer PI control loop integrates
normally.
0
0
x
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
1
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Enabled
0=Disabled
x =Reserved
Bit #
Factory Default Bit Values
PI Enable
PI Hold
PI Reset
Nibble 1
Nibble 2
Nibble 3
Nibble 4
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......