Parameter Descriptions
Chapter 9
Sets the output frequency when a jog command is issued.
Provides an internal fixed speed command value when Speed Ref A = Preset Spd
1...7.
100
Jog Speed
Range:
0 to Maximum Speed [0.1 Hz]
Default:
10.0 Hz
Access:
0
Path:
Speed Command > Discrete Speeds
See also:
101
102
103
104
105
106
107
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
Range:
-/+Maximum Speed [0.1 Hz]
Default:
See
Access:
101...107 = 0
Path:
Speed Command > Discrete Speeds
See also:
90, 93