![Rockwell Automation Allen-Bradley LiquiFlo 2.0 User Manual Download Page 42](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-liquiflo-2-0/allen-bradley-liquiflo-2-0_user-manual_1475412042.webp)
42
Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 3
Planning the Installation
Recommended Motor Lead Lengths
Motor lead lengths can total up to 76 m (250 ft).
Verifying Power Module Output Current Rating Is Greater Than
Chiller Running Load Amps
Verify that the LiquiFlo 2.0 power module output current rating is equal to or
greater than the running load amps (RLA) of the chiller.
lists
the output current values.
Stopping the Drive
Depending on the requirements of the application, the LiquiFlo 2.0 drive can be
programmed to provide either a coast-to-rest or a ramp-to-rest operational stop
without physical separation of the power source from the motor.
• A
coast-to-rest
stop turns off the gate drive to the IGBT power devices.
• A
ramp-to-rest
stop continues to fire the IGBT power devices in a
controlled manner until the motor comes to a stop, and then turns off the
power devices.
You can also program zero speed with power maintained to the motor, but in this
condition, the drive is not actually stopped.
In addition to the operational stop, the LiquiFlo 2.0 power module provides a
hardwired
gate kill
. This function provides a two-wire emergency stop circuit
that does not depend on software or on the transmission of commands over a
communications network. When the two-wire circuit is opened, the gate drive to
the IGBTs is removed.
In Frame 3, the gate kill function is provided by a two-position terminal block
(A33) located on the power module. See
for gate kill connections in
Frame 4.
ATTENTION:
You must provide an external, hardwired emergency stop circuit
outside of the drive circuitry. This circuit must disable the system in case of
improper operation. Uncontrolled machine operation may result if this
emergency stop circuit is not implemented. Failure to observe this precaution
could result in bodily injury.
Summary of Contents for Allen-Bradley LiquiFlo 2.0
Page 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Page 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Page 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Page 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Page 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Page 267: ......