Publication 2094-UM001A-EN-P — September 2006
Connecting the Kinetix 6000 Drive System
85
Wiring the VAC LINE (IPL) Connector
Line Interface Module (IPL connector)
VAC LINE (IPL) Connector
2094-AL09, -AL
xx
S, -BL
xx
S, and -XL75S-C
x
VAC LINE (IPL) Connector
2094-BL02
L3
L2
L1
1 2 3 4
Line Interface Module, Top
V
iew
(2094-XL75
S
-C
x
is shown)
Three-phase Supply
IPL Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
Nm (lb-in)
L1
4
L1
2.5-25
(14-4)
16.0
(0.63)
2.7
(24)
L2
3
L2
L3
2
L3
1
Three-phase Supply
IPL Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
Nm (lb-in)
L1
1
L1
4.0
(12)
10.0
(0.38)
1.5 - 1.8
(13.2 - 15.9)
L2
2
L2
L3
3
L3
4