Publication 2094-UM001A-EN-P — September 2006
126
Configure and Startup the Kinetix 6000 Drive System
6.
Select the Date and Time tab.
7.
Check the box Make this controller the Coordinated System Time
master.
8.
Click OK.
Configure the Logix Module
Follow these steps to configure the Logix module.
1.
Right-click on I/O Configuration in the explorer dialog and select
New Module.
The Select Module dialog opens.
2.
Expand the Motion category and select 1756-M
xx
SE, -L60M03SE,
1768-M04SE, or 1784-PM16SE as appropriate for your actual
hardware configuration.
3.
Click OK.
IMPORTANT
Only one ControlLogix processor can be assigned as the
Coordinated System Time master.