2–6
Troubleshooting and Error Codes
Publication 1336 IMPACT-6.8 – November, 2002
Fault Code and
Text
Suggested Action
Description
Fault
Type
LED Status
02081
Inv Overtemp
Pnd
VP, Flashing green
Warning
An inverter overtemperature is pending.
The inverter heatsink temperature is
approaching the trip level.
Check the cabinet filters, drive fans, and
heatsinks.
Check the thermal sensor and sensor wiring
(connector).
Reduce the load or duty cycle if possible.
Lower the value of PWM Frequency
(parameter 10).
If you do not want this condition to be reported
as a warning, change bit 1 in Warning Select 2
(parameter 23) to 0.
02093
InvOvld Pend
VP, Flashing green
Warning
An inverter (IT) overload is pending. The
inverter current has been in excess of
105% of Inverter Amps (parameter 11)
too long. Continued operation at this
load level will cause an overload.
Reduce the load or duty cycle if possible.
If you do not want this condition to be reported
as a warning, change bit 13 in Warning Select
2 (parameter 23) to 0.
02095
Inv Overload
VP, Flashing green
Warning
Inverter (IT) overload. The inverter
current has been in excess of 105% of
Inverter Amps (parameter 11) too long.
Reduce the load or duty cycle if possible.
If you do not want this condition to be reported
as a warning, change bit 15 in Warning Select
2 (parameter 23) to 0.
03008
HW Malfunction
VP, Red 1 blink
Hard
A hardware malfunction was detected on
power up or reset.
When this condition occurs, the drive
coasts to a stop regardless of the
selected stop type.
Recycle the power. If the fault does not clear,
replace the Control Board.
03009
HW Malfunction
VP, Red 2 blink
Hard
A hardware malfunction was detected on
power up or reset.
When this condition occurs, the drive
coasts to a stop regardless of the
selected stop type.
Recycle the power. If the fault does not clear,
replace the Control Board.
03010
HW Malfunction
VP, Red 3 blink
Hard
A hardware malfunction was detected on
power up or reset.
When this condition occurs, the drive
coasts to a stop regardless of the
selected stop type.
Recycle the power. If the fault does not clear,
replace the Control Board.
03011
HW Malfunction
VP, Red 4 blink
Hard
A hardware malfunction was detected on
power up or reset.
When this condition occurs, the drive
coasts to a stop regardless of the
selected stop type.
Recycle the power. If the fault does not clear,
replace the Control Board.
03012
HW Malfunction
VP, Red 5 blink
Hard
A hardware malfunction was detected on
power up or reset.
When this condition occurs, the drive
coasts to a stop regardless of the
selected stop type.
Recycle the power. If the fault does not clear,
replace the Control Board.
Summary of Contents for Allen-Bradley IMPACT 1336 Series
Page 1: ...Troubleshooting Manual 1336 IMPACT Adjustable Frequency AC Drive 519 597 kW 700 800 HP ...
Page 174: ...7 14 Schematics Publication 1336 IMPACT 6 8 November 2002 This Page Intentionally Left Blank ...
Page 175: ...Notes Publication 1336 IMPACT 6 8 November 2002 ...
Page 176: ...N 2 Publication 1336 IMPACT 6 8 November 2002 ...
Page 177: ...N 3 Publication 1336 IMPACT 6 8 November 2002 ...
Page 178: ...N 4 Publication 1336 IMPACT 6 8 November 2002 ...
Page 179: ...N 5 Publication 1336 IMPACT 6 8 November 2002 ...
Page 180: ...N 6 Publication 1336 IMPACT 6 8 November 2002 ...
Page 181: ...N 7 Publication 1336 IMPACT 6 8 November 2002 ...
Page 182: ...N 8 Publication 1336 IMPACT 6 8 November 2002 ...
Page 183: ...N 9 Publication 1336 IMPACT 6 8 November 2002 ...
Page 184: ...N 10 Publication 1336 IMPACT 6 8 November 2002 ...
Page 185: ...N 11 Publication 1336 IMPACT 6 8 November 2002 ...
Page 186: ...N 12 Publication 1336 IMPACT 6 8 November 2002 ...
Page 187: ...N 13 Publication 1336 IMPACT 6 8 November 2002 ...
Page 188: ...N 14 Publication 1336 IMPACT 6 8 November 2002 ...
Page 194: ...Index I 6 Publication 1336 IMPACT 6 8 November 2002 This Page Intentionally Left Blank ...
Page 195: ......