5–33
Part Replacement Procedures
Publication 1336 IMPACT-6.8 – November, 2002
Replacing the Ground Fault CT
The Ground Fault CT is located at the top of the Inverter Assembly.
Figure 5.18
Ground Fault CT
Gate Driver Board
Inverter Bay w/o Cabinet
(Control Board Not
Shown for Clarity)
Ground Fault CT
DC Input Lines
Removal
!
ATTENTION: Wear a wrist-type grounding strap
when servicing 1336 IMPACT drives. Failure to
protect drive components against ESD may damage
drive components. Refer to Electrostatic Discharge
Precautions at the beginning of this chapter.
1. Remove power and check for zero voltage in the drive. Refer to
Opening the Drive Enclosure in Chapter 3, Access Procedures.
Summary of Contents for Allen-Bradley IMPACT 1336 Series
Page 1: ...Troubleshooting Manual 1336 IMPACT Adjustable Frequency AC Drive 519 597 kW 700 800 HP ...
Page 174: ...7 14 Schematics Publication 1336 IMPACT 6 8 November 2002 This Page Intentionally Left Blank ...
Page 175: ...Notes Publication 1336 IMPACT 6 8 November 2002 ...
Page 176: ...N 2 Publication 1336 IMPACT 6 8 November 2002 ...
Page 177: ...N 3 Publication 1336 IMPACT 6 8 November 2002 ...
Page 178: ...N 4 Publication 1336 IMPACT 6 8 November 2002 ...
Page 179: ...N 5 Publication 1336 IMPACT 6 8 November 2002 ...
Page 180: ...N 6 Publication 1336 IMPACT 6 8 November 2002 ...
Page 181: ...N 7 Publication 1336 IMPACT 6 8 November 2002 ...
Page 182: ...N 8 Publication 1336 IMPACT 6 8 November 2002 ...
Page 183: ...N 9 Publication 1336 IMPACT 6 8 November 2002 ...
Page 184: ...N 10 Publication 1336 IMPACT 6 8 November 2002 ...
Page 185: ...N 11 Publication 1336 IMPACT 6 8 November 2002 ...
Page 186: ...N 12 Publication 1336 IMPACT 6 8 November 2002 ...
Page 187: ...N 13 Publication 1336 IMPACT 6 8 November 2002 ...
Page 188: ...N 14 Publication 1336 IMPACT 6 8 November 2002 ...
Page 194: ...Index I 6 Publication 1336 IMPACT 6 8 November 2002 This Page Intentionally Left Blank ...
Page 195: ......