GuardPLC Digital Input/Output Module
11
Rockwell Automation Publication 1753-IN003C-EN-P - June 2010
Digital Output Terminals
Terminals accommodate wires up to 1.5 mm
2
(16 AWG). See the terminal torque specifications
. Digital outputs (DO) are connected to these terminals.
Example: Connecting Actuators to the Outputs
Terminal Number
Designation
Function
1
L-
Reference pole
2
1
Digital output 1
3
2
Digital output 2
4
3
Digital output 3
5
4
Digital output 4
6
L-
Reference pole
7
L-
Reference pole
8
5
Digital output 5
9
6
Digital output 6
10
7
Digital output 7
11
8
Digital output 8
12
L-
Reference pole
TIP
Inductive loads can be connected without a protection diode on the load.
However, Rockwell Automation strongly recommends that a protection
diode be fitted directly to the load to suppress any interference voltage. A
1N4004 diode is recommended.
ATTENTION:
Pulse outputs may not be used as safety-related outputs.
1 2 3 4 5 6
1 2 3 4
1
L-
L-
DO
2
(2A)
3 4
5 6
7 8 9 10 11 12
7 8 9 10
5
L-
L-
DO
6
(2A)
7 8
11 12
DO 1
DO 2
DO 3
DO 4
L-
L-