Rockwell Automation Publication 1794-IN082F-EN-P - October 2022

3

FLEX I/O EtherNet/IP Adapters Installation Instructions

Environment and Enclosure

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/

IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such 

environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific 

environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The 

enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 

5V A or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of 

this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety 

certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1

, for additional installation requirements.

• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

ATTENTION: 

Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this 

equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring 

instructions in addition to requirements of all applicable codes, laws, and standards.

Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in 

accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to 

the manufacturer for repair. Do not dismantle the module.

North American Hazardous Location Approval

The Following Information Applies When Operating This Equipment In 

Hazardous Locations.

Informations sur l’utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 

Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each 

product is supplied with markings on the rating nameplate indicating the 

hazardous location temperature code. When combining products within a system, 

the most adverse temperature code (lowest "T" number) may be used to help 

determine the overall temperature code of the system. Combinations of equipment 

in your system are subject to investigation by the local Authority Having 

Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en 

environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. 

Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le 

code de température pour les environnements dangereux. Lorsque plusieurs produits sont 

combinés dans un système, le code de température le plus défavorable (code de 

température le plus faible) peut être utilisé pour déterminer le code de température global 

du système. Les combinaisons d'équipements dans le système sont sujettes à inspection 

par les autorités locales qualifiées au moment de l'installation.

WARNING:

Explosion Hazard –

• Do not disconnect equipment unless power has been 

removed or the area is known to be nonhazardous. 

• Do not disconnect connections to this equipment unless 

power has been removed or the area is known to be 

nonhazardous. Secure any external connections that 

mate to this equipment by using screws, sliding latches, 

threaded connectors, or other means provided with this 

product.

• Substitution of components may impair suitability for 

Class I, Division 2.

AVERTISSEMENT:

Risque d’Explosion – 

• Couper le courant ou s'assurer que l'environnement est classé 

non dangereux avant de débrancher l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé 

non dangereux avant de débrancher les connecteurs. Fixer tous 

les connecteurs externes reliés à cet équipement à l'aide de vis, 

loquets coulissants, connecteurs filetés ou autres moyens 

fournis avec ce produit.

• La substitution de composants peut rendre cet équipement 

inadapté à une utilisation en environnement de Classe I, Division 

2.

UK and European Hazardous Location Approval

The following applies to products marked 

 II 3 G:

• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment 

given in Schedule 1 of UKEX and Annex II of EU Directive 2014/34/EU. See the UKEx and EU Declaration of Conformity at 

rok.auto/certifications

 for details.

• The type of protection is Ex ec IIC T4 Gc according to EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018 and 

EN IEC 60079-7:2015+A1:2018, Explosive atmospheres. Equipment protection by increased safety "e".

• Comply to Standard EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018, EN IEC 60079-7:2015+A1:2018 

Explosive atmospheres. Equipment protection by increased safety "e", reference certificate number DEMKO 14 ATEX 1342501X and UL22UKEX2378X.

• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short 

periods. Such locations correspond to Zone 2 classification according to UKEX regulation 2016 No. 1107 and ATEX directive 2014/34/EU.

• May have catalog numbers followed by a "K" to indicate a conformal coating option.

IEC Hazardous Location Approval

The following applies to products with IECEx certification:

 

• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for 

short periods. Such locations correspond to Zone 2 classification to IEC 60079-0.

• The type of protection is Ex ec IIC T4 Gc according to IEC 60079-0 and IEC 60079-7.

• Comply to Standards IEC 60079-0, Explosive atmospheres Part 0: Equipment - General requirements, Edition 7, Revision Date 2017, IEC 60079-7, 5.1 Edition revision date 

2017, Explosive atmospheres - Part 7: Equipment protection by increased safety "e", reference IECEx certificate number IECEx UL 14.0066X.

Summary of Contents for Allen-Bradley FLEX 1794-AENT

Page 1: ...pic Page Summary of Changes 1 Overview 5 Install Your Adapter 5 Mount the Adapter on a DIN Rail 6 Mount on a Panel or Wall 6 Mount or Replace the Adapter on an Existing System 6 Connect Wiring 7 Set the Network Address 8 Indicators 9 Specifications 10 Topic Page Updated UK and European Hazardous Location Approval 3 Updated IEC Hazardous Location Approval 3 Updated Special Conditions for Safe Use 4...

Page 2: ...façon qui n a pas été définie par le fabricant la protection fournie par l équipement peut être compromise ATTENZIONE Prima di installare configurare ed utilizzare il prodotto o effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli ...

Page 3: ... identification qui indiquent le code de température pour les environnements dangereux Lorsque plusieurs produits sont combinés dans un système le code de température le plus défavorable code de température le plus faible peut être utilisé pour déterminer le code de température global du système Les combinaisons d équipements dans le système sont sujettes à inspection par les autorités locales qua...

Page 4: ...not touch circuit components inside the equipment Use a static safe workstation if available Store the equipment in appropriate static safe packaging when not in use ATTENTION Special Conditions for Safe Use This product is grounded through the DIN rail to chassis ground Use zinc plated chromate passivated steel DIN rail to assure proper grounding The use of other DIN rail materials for example al...

Page 5: ...transfer across an EtherNet IP network between FLEX I O modules and a controller EtherNet IP Adapter Install Your Adapter Component Identification 1 EtherNet IP adapter 2 Flexbus connector 3 24V common connections 4 24V DC connections 5 IP address switches 6 Adapter DIN rail locking tab 7 Network cable RJ45 connector underside 8 MAC ID label 9 Status indicators 1 9 8 7 6 5 4 3 2 1794 AENT B A B C ...

Page 6: ...mber 1794 NM1 B Mount or Replace the Adapter on an Existing System 1 Remove the Ethernet plug in connector from the bottom of the adapter 2 Disconnect any adapter wiring that is jumpered to the adjacent terminal base 3 Disconnect any user power wiring connections to the adapter 4 Using a screwdriver or similar tool open the module locking mechanism and remove the module from the base unit to which...

Page 7: ...eft side of the lower connector terminal C 4 Use connectors D and E to pass 24V common D and 24V DC power E to the next module in the series WARNING If you connect or disconnect the communication cable with power applied to the adapter or any device on the network an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area...

Page 8: ...he number set on the switches The subnet mask of the adapter is 255 255 255 0 and the gateway address is set to 0 0 0 0 The adapter does not have a host name assigned or use any Domain Name System when using the thumbwheel settings Network Address Thumbwheel If you set the switches to an invalid number such as 000 or a value greater than 254 the adapter checks to see if you enabled DHCP The switch...

Page 9: ...elf test Wait until completed Network Status Indicators Indicator Status Description Network Status Indicator Off not powered no IP address Adapter is not powered or does not have an IP address Verify that there is power and the adapter is correctly wired to the power supply Make sure that the adapter is configured Flashing green no connections Adapter has obtained an IP address but has no establi...

Page 10: ...ng as described in the appropriate System Level Installation Manual and see Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 for more information 1 on power ports 2 on communications ports Terminal screw torque 0 8 N m 7 lb in Environmental Specifications Attribute Value Temperature operating IEC 60068 2 1 Test Ad operating cold IEC 60068 2 2 Test Bd operating dry heat IE...

Page 11: ...ith EN 63000 Technical documentation RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex UK Statutory Instrument 2016 No 1107 and European Union 2014 34 EU ATEX Directive compliant with EN IEC 60079 0 General Requirements EN IEC 60079 7 Explosive Atmospheres Protection e II 3 G Ex ec IIC T4 Gc DEMKO 14 ATEX 1342501X UL22UKEX2378X IECEx IECEx System compliant ...

Page 12: ...lected separately from any unsorted municipal waste Rockwell Automation Support Use these resources to access support information Documentation Feedback Your comments help us serve your documentation needs better If you have any suggestions on how to improve our content complete the form at rok auto docfeedback Technical Support Center Find help with how to videos FAQs chat user forums Knowledgeba...

Reviews: