Rockwell Automation Publication 193-UM015D-EN-P - February 2015
335
Metering and Diagnostics
Chapter 8
configuration value for Power Scale (Parameter 377). When Single or Three
Phase (Parameter 176) is set to
Three Phase
, Total Reactive Power is calculated as
follows:
Total Reactive Power = (L1 Reactive Power + L2 Reactive Power + L3 Reactive
Power)
When Single or Three Phase (Parameter 176) is set to
Single Phase
, Total
Reactive Power is calculated as follows:
Total Reactive Power = (L1 Reactive Power + L2 Reactive Power)
Table 420 - Total Reactive Power (Parameter 71)
L1 Apparent Power
L1 Apparent Power (Parameter 72) reports the apparent power for line 1 in kVA
or MVA depending on the configuration value for Power Scale (Parameter 377).
When Voltage Mode (Parameter 352) is set to any
Delta
base setting, L1
Apparent Power is set to 0.
Table 421 - L1 Apparent Power (Parameter 72)
L2 Apparent Power
L2 Apparent Power (Parameter 73) reports the apparent power for line 2 in kVA
or MVA depending on the configuration value for Power Scale (Parameter 377).
When Voltage Mode (Parameter 352) is set to any
Delta
base setting, L2
Apparent Power is set to 0.
Default Value
0.000c
Minimum Value
-2000000.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVAR or MVAR
Default Value
0.000
Minimum Value
0.000
Maximum Value
2000000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVA or MVA
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......