Chapter 2
Installation and Wiring
193-DNCT-BZ1 Physical Connections
The optional Cat. No. 193-DNCT-BZ1 connects to the DeviceNet™ network via
an attached cable that has color coded bare leads. The cable’s bare leads are wired
to a DeviceNet™ connector according to the following table:
Powering the 193-DNCT
The DNCT must be powered from an external 24V DC source through the
communication cable. The 24V DC connections should be made to the V+ and
V- pins/wires in the above cable pinout/wire definitions.
ATTENTION:
When mounting in a door or panel-mounted bezel kit,
only the Cat. No. 193-DNCT-BZ1 DeviceNet™ Bezel Kit should be used
with the Bulletin 193-DNCT DeviceNet™ Configuration Terminal.
Signal
Function
Color
V-
Common
Black
Can_L
Signal Low
Blue
Drain
Shield
Non-insulated
Can_H
Signal High
White
V+
Power Supply
Red
ATTENTION:
Before physically connecting the DNCT to a target device,
verify that the external power supply has adequate capacity to power all
devices on the network.