Publication CNET-IN002A-EN-P - December 2001
3-2
Install a ControlNet Coax Media System
Install the Trunk Cable
Install your trunk cable, observing your cable supplier’s installation
instructions and these guidelines.
Wire the External to Enclosures
When you pull the RG-6 type Coax cable through multiple conduit
bends, follow these specifications.
Wire Inside Enclosures
When you do not pull the RG-6 type Coax cable through conduit,
follow these specifications.
Mount the Taps
To mount the taps you:
•
select where you want to mount the taps based on the topology
design that you planned in Chapter 2 of this manual.
•
mount the taps
Select Where To Mount The Taps
•
There is no spacing requirement between taps; you can install
two adjacent taps if necessary by using a barrel connector
(1786-BNCP).
•
Be certain that the location where you are going to mount a tap
is convenient for your cable route.
For this Coax
cable:
The pull strength
should not exceed:
The bend radius should
not exceed:
PVC
42.75kg (95lbs)
76.2mm (3.0”)
FEP
61.65kg (137lbs)
69.9mm (2.75”)
For this Coax cable:
The bend radius should not
exceed:
PVC
38.1mm (1.5”)
FEP
35.6mm (1.4”)
Tap drop-cable
25.4mm (1.0”)
Summary of Contents for Allen-Bradley ControlNet 1786 Series
Page 1: ...ControlNet Coax Media Planning and Installation Guide 1786 series Installation Instructions...
Page 6: ...Publication CNET IN002A EN P December 2001 4 Notes...
Page 60: ...Publication CNET IN002A EN P December 2001 3 24 Install a ControlNet Coax Media System Notes...
Page 70: ...Publication CNET IN002A EN P December 2001 4 Index...
Page 73: ......