Appendix D Cable Connections and Communication
CompactLogix 5370
Controller Cable Charts
Support for communication with CompactLogix™ 5370 L1 controllers has been
added from firmware revision 3.011 onwards. Support for communication
with CompactLogix 5370 L2 and L3 controllers have been added from firmware
revision 4.012 onwards. This feature also requires Connected Components
Workbench software version 9 or later to be installed.
The chart provides a summary of terminal connections to controllers and
network interface modules.
For more information on adding CompactLogix 5370 controllers to your
applications, see the DesignStation help in Connected Components
Workbench software on the following topics.
•
Configuring communication settings for CompactLogix 5370 controllers.
•
Mapping tags from CompactLogix 5370 controllers to PanelView 800
terminals.
•
Validating an application that includes a CompactLogix 5370 controller.
Ethernet Connection
The PanelView 800 terminals have an Ethernet port that supports:
•
communication to a controller.
•
connection to a computer for accessing the PanelView Explorer Startup
window and downloading applications from Connected Components
Workbench software to the terminal.
Ethernet Connector
The base-configured unit of the terminals has an RJ45, 10/100 Base-T
connector for Ethernet network communication.
PanelView 800 Terminal Connections to CompactLogix 5370 Controllers
Protocol (CIP)
PanelView 800 Port
CompactLogix 5370
Ethernet
(CompactLogix)
2711P-CBL-EX04
(CAT5 Ethernet)
2711P-CBL-EX04
(CAT5 Ethernet)
Ethernet Connector Pinout
Pin
Pin
Pin Name
Looking into RJ45
Connector
1
TD+
2
TD-
3
RD+
4
NC
5
NC
6
RD-
7
NC
8
NC
Shield Connection
Chassis Gnd
Ethernet port
2711R-T4T
2711R-T7T
2711R-T10T
1
8