![Rockwell Automation Allen-Bradley 2094-BC01-M01-S User Manual Download Page 168](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-2094-bc01-m01-s/allen-bradley-2094-bc01-m01-s_user-manual_1475821168.webp)
168
Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 7
Troubleshooting the Kinetix 6000 Drive System
Presence of noise on command
or motor feedback signal wires.
Recommended grounding per installation instructions have not
been followed.
•
Verify grounding.
•
Route wire away from noise sources.
•
Refer to System Design for Control of
Electrical Noise, publication
Line frequency may be present.
•
Verify grounding.
•
Route wire away from noise sources.
Variable frequency may be velocity feedback ripple or a disturbance
caused by gear teeth or ballscrew balls, for example. The frequency
may be a multiple of the motor power transmission components or
ballscrew speeds resulting in velocity disturbance.
•
Decouple the motor for verification.
•
Check and improve mechanical performance,
for example, the gearbox or ballscrew
mechanism.
No rotation
The motor connections are loose or open.
Check motor wiring and connections.
Foreign matter is lodged in the motor.
Remove foreign matter.
The motor load is excessive.
Verify the servo system sizing.
The bearings are worn.
Return the motor for repair.
The motor brake is engaged (if supplied).
•
Check brake wiring and function.
•
Return the motor for repair.
The motor is not connect to the load.
Check coupling.
Motor overheating
The duty cycle is excessive.
Change the command profile to reduce
accel/decel or increase time.
The rotor is partially demagnetized causing excessive motor
current.
Return the motor for repair.
Abnormal noise
Motor tuning limits are set too high.
Run Tune in RSLogix 5000 software.
Loose parts are present in the motor.
•
Remove the loose parts.
•
Return motor for repair.
•
Replace motor.
Through bolts or coupling is loose.
Tighten bolts.
The bearings are worn.
Return motor for repair.
Mechanical resonance.
Notch filter may be required (refer to Axis
Properties dialog box, Output tab in
RSLogix 5000 software).
Erratic operation - Motor
locks into position, runs
without control or with
reduced torque.
Motor power phases U and V, U and W, or V and W reversed.
Check and correct motor power wiring.
Sine, Cosine or Rotor leads are reversed in the feedback cable
connector.
Check and correct motor feedback wiring.
Sine, Cosine, Rotor lead sets of resolver feedback are reversed.
Check and correct motor feedback wiring.
Table 93 - General System Anomalies (Continued)
Condition
Potential Cause
Possible Resolution
Summary of Contents for Allen-Bradley 2094-BC01-M01-S
Page 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Page 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Page 279: ......