Wire the Motor/Resistive Brake (BC) Connector
This example applies to AM modules and the inverter section of IAM modules.
Figure 58 - IAM/AM Module (BC connector)
24V DC Brake Input Power Connections
RBM Module Connections
Table 63 - Motor/Resistive Brake (BC) Connector
MBRK-
MBRK+
COM
P
W
R
DBRK-
DBRK+
1 2 3 4 5 6
Kinetix 6000 IAM/AM Module
(IAM module is shown)
Motor/Resistive Brake
(BC) Connector
IMPORTANT
If your system includes a LIM module, you can source the 24V DC from
the LIM module (P1L or PSL connector).
Table 62 - Motor/Resistive Brake (BC) Connector
2094-AL
xx
S, 2094-BL
xx
S,
2094-XL75S-C
x
LIM Modules
2094-AL09 and 2094-BL02
LIM Modules
BC Connector
(IAM/AM modules)
P1L Pin
Signal
PSL Pin
Signal
BC Pin
Signal
1
IO_PWR2
1
MBRK PWR
3
PWR
2
IO_COM2
2
MBRK COM
4
COM
RBM Module I/O Connections
BC Connector
(IAM/AM modules)
TB3 Pin
Signal
MP Pin
Signal
(1)
(1) Firmware revision 1.071 or later, is required to use the DBRK outputs on the Kinetix 6000 IAM/AM
module.
6
COIL_A1
1
DBRK+
7
COIL_A2
2
DBRK-
Summary of Contents for Allen-Bradley 2094-BC01-M01-S