Publication 1794-6.5.12 - September 2011
Calibrate Your Module
43
5
Channel 5 Input Data
6
Channel 6 Input Data
7
Channel 7 Input Data
8
Overrange Alarm Bits (channel 0 = bit 08, and so on.) Underrange Alarm Bits (channel 0 = bit 00, and so on.)
9
Ch7
Flt
Ch6
Flt
Ch5
Flt
Ch4
Flt
Ch3
Flt
Ch2
Flt
Ch1
Flt
Ch0
Flt
CJC 2
Flt
CJC 1
Flt
SAB
Diagnostic Status
10
EDT command response
EDT data response
Where:
Flt = Fault
CJC = Cold Junction Compensation
SAB = Series of unit; 0 = Series A; 1 = Series B
Read Words for Calibration
Decimal
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Word
⇓
Read
ATTENTION
The CJC Status bit, Read Word 9, Bit 3 is added with the Firmware C
release of the 1794-IRT8 Series B module.
The CJC Status bit is turned On when the temperature between the
CJCs is greater than 6 °C but less than 12 °C.
When this temperature difference is above 12 °C, then the CJC Alarm
bits are set.
Also, if a CJC temperrature is over-range or under-range, then the
associated CJC Alarm bit is set. In this condition, the CJC Status bit is
not set.
The CJC Status bit does not exist in Series A.
Summary of Contents for Allen-Bradley 1794-IRT8K
Page 4: ...Publication 1794 6 5 12 September 2011 iv Summary of Changes Notes ...
Page 8: ...Publication 1794 6 5 12 EN E September 2011 viii Table of Contents Notes ...
Page 62: ...Publication 1794 6 5 12 September 2011 50 Calibrate Your Module Notes ...
Page 84: ...Publication 1794 6 5 12 September 2011 72 Index Notes ...
Page 85: ...Publication 1794 6 5 12 September 2011 Index 73 ...