20 DeviceNet Base RTD and Thermocouple CompactBlock LDX I/O
Publication 1790-IN011C-EN-P - January 2015
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…55 °C (32…131 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…90% non-condensing
Operating altitude
2000 m
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
10 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz
10V/m with 200 Hz 50% Pulse 100%AM @ 900 MHz
EFT/B immunity
IEC 61000-4-4:
1 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
±2 kV @ 5 kHz on communications ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz