Error Codes
This table indicates the error codes that are associated with the 1769-ASCII
module.
Configuration Errors
This table indicates the error codes that are associated with configuration errors.
Table 10 - 1769-ASCII Module Error Codes
Value (Hex)
Meaning
0
No error
200…3FF
Hardware error
400…5FF
Configuration error
800…DFF
Reserved for future use
E00…FFF
Bus master detected error
Table 11 - Global Module Configuration Errors
Value
(Hex)
Meaning
Description
0
No error
The 1769-ASCII module has no module-specific errors.
401
Max output array size
exceeded
The maximum output array size is too large.
In alternating mode, channel 0 and channel 1 must have less than 496
transmit bytes.
In simultaneous mode, channel 0 and channel 1 must have less than 496
transmit bytes collectively.
402
Max input array size
exceeded
The maximum input array size is too large.
In alternating mode, channel 0 and channel 1 must have less than 496
receive bytes.
In simultaneous mode, channel 0 and channel 1 must have less than 496
receive bytes collectively.