Chapter 5
Configure the Module in a GuardLogix Controller System
6.
Click OK again to apply your changes.
The I/O Configuration tree displays the 1734-OB8S module.
Configure the Safety Digital Outputs
Follow this procedure to configure the safety digital outputs.
1.
From the Module Properties dialog box, click the Output Configuration
tab.
2.
Assign the Point Operation Type.
3.
Assign the Point Mode.
Choose
Description
Single
The output is treated as a single channel.
Dual (default)
The POINT Guard I/O module treats the outputs as a pair. It always sets them HI or LO as a
matched pair. Safety logic must set both of these outputs ON or OFF at the same time or
the module declares a channel fault.
Choose
Description
Not Used
The output is disabled.
Safety
The output point is enabled and does not perform a pulse test on the output.
Safety Pulse
Test
The output point is enabled and performs a pulse test on the output. When the output is
energized, the output pulses low briefly. The pulse test detects whether the output is
functioning properly.
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......