Bulletin 1609-D Installation Instructions
Mount the UPS
The UPS-D is designed to mount on the back of the panel or to the floor of the
enclosure. The UPS mounts to a bracket assembly (1609-BRK) that allows it
to mount to either the panel or floor.
Figure 1 - Mounting the UPS
Hardwire UPS
Wiring of the UPS must be performed by a qualified electrician using the
appropriate wire gauges.
Selection of Cables
Table 1 - AC Main Input/Output Wiring for UPS:
Table 2 - DC Input / Output Wiring for External Battery Cabinet:
Item Specification
Wire Size
14 AWG
Minimum temperature
75 °C (167 °F)
Wire conductor material
Copper only
Tightening torque for terminals
4.4 lb-in.
Item Specification
Wire Size
10 AWG
Minimum temperature
75 °C (167 °F)
Wire conductor material
Copper only
Tightening torque for terminals
12 lb-in.
WARNING:
To reduce the risk of fire, connect only to a circuit with 20 amperes
maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.
A disconnect switch must be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent
protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.