18
Rockwell Automation Publication 1609-UM009D-EN-P - February 2021
1609-EXBAT Installation Instructions
Selection of Cables
Table 4 - DC Input/Output Wiring for External Battery Cabinet
Connect 1609-EXBAT to the
UPS
To install the 1609-EXBAT unit with the 1609-D UPS, connect the three 10
AWG wires from the 1609-EXBAT terminals to the 1609-D UPS terminals
marked as EXTERNAL BATT PACK (36V).
Dispose of used batteries according to the battery instructions.
Figure 10 - System Wiring
Item Specification
Wire Size
10 AWG
Minimum temperature
75 °C (167 °F)
Wire conductor material
Copper only
Tightening torque for terminals
12 lb-in.