Rockwell Automation Publication 1609-UM009D-EN-P - February 2021
13
1609-B Installation Instructions
Mount the UPS
The 1609-B UPS products are designed to mount to a heavy-duty DIN-rail. The
1609-B UPS products are also designed with an optional bracket assembly
(catalog number 1609-BRK) that allows it to mount to either the panel or floor.
Figure 4 - Standard DIN-Rail Mount
Figure 5 - Optional Panel or Floor Mount
Hardwire UPS
Wiring of the UPS should be performed by a qualified electrician using the
appropriate wire gauges.
Selection of Cables
Table 3 - AC Main Input / Output Wiring for UPS
Item
Specification
Wire Size
14 AWG
Minimum Temperature
75 °C (167 °F)
Wire Conductor Material
Copper only
Tightening Torque for Terminals
4.4 lb• in.
WARNING:
To reduce the risk of fire, connect only to a circuit with 20 amperes
maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.
A disconnect switch must be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent
protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.