![Rockwell Automation Allen-Bradley 1606-XLE240E Reference Manual Download Page 34](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-1606-xle240e/allen-bradley-1606-xle240e_reference-manual_1475568034.webp)
34
Rockwell Automation Publication 1606-RM101A-EN-P - July 2020
Use in a Tightly Sealed
Enclosure
When the power supply is installed in a tightly sealed enclosure, the
temperature inside the enclosure is higher than outside. In such situations, the
inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the
temperature rise inside the enclosure.
The power supply is placed in the middle of the box. No other heat producing
items are inside the box.
The temperature sensor inside the box is placed in the middle of the right side
of the power supply with a distance of 1 cm (0.39 in.).
Attributes
Case A
Case B
Case C
Case D
Enclosure size
110 x 180 x 165 mm
(4.33 x 7.09 x 6.50 in.)
Rittal Typ IP66 Box
PK 9516 100, plastic
110 x 180 x 165 mm
(4.33 x 7.09 x 6.50 in.)
Rittal Typ IP66 Box
PK 9516 100, plastic
180 x 180 x 165 mm
(7.09 x 7.09 x 6.50 in.)
Rittal Typ IP66 Box
PK 9519 100, plastic
180 x 180 x 165 mm
(7.09 x 7.09 x 6.50 in.)
Rittal Typ IP66 Box
PK 9519 100, plastic
Input voltage
230V AC
230V AC
230V AC
230V AC
Load
24V, 8 A; (=80%)
24V, 10 A; (=100%)
24V, 8 A; (=80%)
24V, 10 A; (=100%)
Temperature inside the box
48.6 °C (119.48 °F)
53.8 °C (128.84 °F)
42.0 °C (107.6 °F)
48.1 °C (118.58 °F)
Temperature outside the box
26.3 °C (79.34 °F)
26.6 °C (79.88 °F)
25.8 °C (78.44 °F)
26.2 °C (79.16 °F)
Temperature rise
22.3 K (40.14 °F)
27.2 K (48.96 °F)
16.2 K (29.16 °F)
21.9 K (39.42 °F)