Electromagnetic
Compatibility
The power supply is suitable for applications in industrial, residential,
commercial, and light industrial environments.
The following table provides electromagnetic compatibility (EMC) immunity
information according to generic standards EN 61000-6-1 and EN 61000-6-2.
The following table provides EMC Emissions information according to generic
standards EN 61000-6-3 and EN 61000-6-4.
The following table provides switching frequencies.
Attributes
Standards
Values
Criteria
(1)
(1)
Criterion A: Power supply shows normal operation behavior within the defined limits.
Criterion C: Temporary loss of function is possible. Power supply may shut down and restart by itself. No damage or hazards
for the power supply occur.
Electrostatic discharge
EN 61000-4-2
Contact discharge Air discharge
8 kV
Criterion A
15 kV
Criterion A
Electromagnetic RF field
EN 61000-4-3
80 MHz…2.7 GHz
20V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
4 kV
Criterion A
Output lines
2 kV
Criterion A
DC OK signal (coupling clamp)
2 kV
Criterion A
Surge voltage on input
EN 61000-4-5
L to N
2 kV
Criterion A
L to PE, N to PE
4 kV
Criterion A
Surge voltage on output
EN 61000-4-5
+ to -
1 kV
Criterion A
+/- to PE
2 kV
Criterion A
Surge voltage on Signals
EN 61000-4-5
DC OK Signal to PE
1 kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15…80 mHz
20V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 100V AC
0V AC, 20 ms
Criterion A
40% of 100V AC
40V AC, 200 ms
Criterion C
70% of 100V AC
70V AC, 500 ms
Criterion C
0% of 200V AC
0V AC, 20 ms
Criterion A
40% of 200V AC
80V AC, 200 ms
Criterion A
70% of 200V AC
140V AC, 500 ms
Criterion A
Voltage interruptions
EN 61000-4-11
0% of 200V AC (=0V)
5000 ms
Criterion C
Voltage sags
SEMI F47 0706
Dips on the input voltage according to SEMI F47 standard
80% of 120V AC (96V AC)
1000 ms
Criterion A
70% of 120V AC (84V AC)
500 ms
Criterion A
50% of 120V AC (60V AC)
200 ms
Criterion A
Powerful transients
VDE 0160
Over entire load range
750V, 0.3 ms
Criterion A
Attributes
Standards
Notes
Conducted emission input lines
EN 55011, EN 55015, EN 55022, FCC
Part 15, CISPR 11, CISPR 22
Class B
Conducted emission output lines
(1)
(1)
For information only, not mandatory for EN 61000-6-3.
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Limits for DC power port according to EN
61000-6-3 fulfilled
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
Class A fulfilled between 0…12 A load Class
C fulfilled between 6…12 A load
Voltage fluctuations, flicker
EN 61000-3-3
Fulfilled
(2)
(2) Tested with constant current loads, non-pulsing.
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation
Converters
Frequencies
Notes
PFC converter
110 kHz
Fixed frequency
Main converter
84…140 kHz
Output load dependent
Auxiliary converter
60 kHz
Fixed frequency