Power Supply - 12V, 10 A, 120 W, 

Single-phase Input

Catalog Number 1606-XLE120B

Reference Manual

Original Instructions

Summary of Contents for Allen-Bradley 1606-XLE120B

Page 1: ...Power Supply 12V 10 A 120 W Single phase Input Catalog Number 1606 XLE120B Reference Manual Original Instructions...

Page 2: ...Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permi...

Page 3: ...tent 12 Efficiency and Power Losses 13 Functional Diagram 14 Front Side and User Elements 14 Connection Terminals 15 Lifetime Expectancy 16 Mean Time Between Failure 16 Electromagnetic Capability 17 E...

Page 4: ...4 Rockwell Automation Publication 1606 RM109A EN P August 2020 Power Supply 12V 10 A 120 W Single Phase Notes...

Page 5: ...tures up to 45 C 113 F Additionally it can deliver three times the nominal output current for 12 ms which helps to trip fuses on faulty output branches The power supply features high immunity to trans...

Page 6: ...0 C 113 158 F Input Voltage AC 100 240V 15 10 Frequency 50 60 Hz 6 Input Current AC 1 09 0 6 A At 120 230V AC Power Factor 0 98 0 91 At 120 230V AC Input Voltage DC 110 150V DC 20 Input Current DC 1 2...

Page 7: ...t factor Typ 1 7 1 8 2 2 At 12V 10 A The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform Startup delay Typ 400 ms 350 ms 375 ms See Figure 2 Rise ti...

Page 8: ...lfunction or damage the unit Connect pole to L pole to N and the PE terminal to an earth wire or to the machine ground Attribute Value Notes DC input Nom DC 110 150V 20 DC input range Min 88 180V DC C...

Page 9: ...h on 100V AC 120V AC 230V AC Inrush current Max 8 Apeak 7 Apeak 7Apeak At 40 C 104 F cold start Typ 5 Apeak 4 Apeak 4Apeak At 25 C 77 F cold start Typ 5 Apeak 5 Apeak 6Apeak At 40 C 104 F cold start I...

Page 10: ...At 12V and 60 C 140 F ambient temperature 7 5 A At 12V and 70 C 158 F ambient temperature 9 6 A 2 2 At heavy overloads when output voltage falls below 7V the power supply delivers continuous output c...

Page 11: ...t Voltage 0 0 1 2 2 4 6 15V 8 10 12 20 A 8 2 4 10 14 16 6 1 8 Adjustment Range Output Current A continuous current B intermittent current A B Output Voltage dynamic behavior 12ms 0 0 2 4 6 15V 8 10 12...

Page 12: ...s 35 ms At 12V 10 A see Figure 11 Min 27 ms 27 ms 27 ms At 12V 10 A see Figure 11 Figure 11 Hold up Time Versus Input Voltage Figure 12 Shutdown Behavior Definitions 0 15 30 45 60 90 ms 90 120 155 190...

Page 13: ...25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time...

Page 14: ...t r Inrush Current Limiter V OUT L N DC OK Contact DC Ok Status Indicator DC OK Relay Figure 18 Front Side User Elements 1 Input Terminals N L N L Line Input PE Protective Earth Input 2 Output Termina...

Page 15: ...Screwtermination Screwtermination Push intermination Solid wire Max 6 mm2 6 mm2 1 5 mm2 Stranded wire Max 4 mm2 4 mm2 1 5 mm2 American Wire Gauge AWG 20 10 AWG 20 10 AWG 24 16 Max wire diameter includ...

Page 16: ...ally one unit will fail every 100 hours if 10 000 units are installed in the field However it can not be determined if the failed unit has been running for 50 000 hr or only for 100 hr For these types...

Page 17: ...ed EN 61000 4 6 0 15 80 MHz 20V CriterionA Mains voltage dips EN 61000 4 11 0 of100V AC 40 of100V AC 70 of100V AC 0 of200V AC 40 of200V AC 40 of200V AC 70 of200V AC 0V AC 20 ms 40V AC 200 ms 70V AC 50...

Page 18: ...ft Degree of pollution 2 According to IEC 62477 1 not conductive Vibration sinusoidal 2 17 8 Hz 1 6 mm 17 8 500 Hz 2 g According to IEC 60068 2 6 Shock 30 g 6 ms 20 g 11 ms 3 bumps direction 18 bumps...

Page 19: ...rth connection is required Degree of protection IP 20 AccordingtoEN IEC60529 Over temperature protection Included Output shut down with automatic restart Temperature sensors are installed on critical...

Page 20: ...set the cut off current settings to the value in the table below Figure 23 Dialectic Strength IMPORTANT Connect either the pole or the pole to the protective earth system This helps to avoid situatio...

Page 21: ...t Control and Laboratory Use Particular requirements for control equipment Applicable for US and Canada E File E56639 CE EU Declaration of Conformity Trade conformity assessment for Europe The CE mark...

Page 22: ...ight of 7 5 mm 30 in or 15 mm 60 in Housing material Body Aluminum alloy Cover Zinc plated steel Installation clearances Keep the following installation clearances 40 mm 1 57 in on top 20 mm 0 79 in o...

Page 23: ...acket is used to mount the devices on a wall panel without utilizing a DIN rail The bracket can be mounted without detaching the DIN rail brackets All dimensions in the following figures are in millim...

Page 24: ...pled by utilizing MOSFET technology The inputs can also be operated up to 24A when the ambient temperature does not exceed 45 C 113 F The output can be loaded with nominal 20A at 70 C 158 F or 24A at...

Page 25: ...individually protected with circuit breakers or fuses In case of a short or an overload in one branch circuit the fuse or circuit breaker need a certain amount of over current to open in a timely man...

Page 26: ...d at no load and at the battery end of the cable very precisely to the end of charge voltage The voltage should be set to 13 9V at 10 C 50 F ambient temperature 13 75V at 20 C 68 F ambient temperature...

Page 27: ...where a reduction of the output current is required for example altitude Leakage current EMI inrush current will increase when using multiple devices Parallel Use for Redundancy 1 1 Redundancy Device...

Page 28: ...output current is required For N 1 redundancy the ambient temperature is not allowed to exceed 40 C 104 F Wiring Examples Figure 33 1 1 Redundant Configuration for 10 A Load Current with a Dual Redund...

Page 29: ...the inside temperature defines the ambient temperature for the device In the following test setup the device is placed in the middle of the box no other heat producing items are inside the box The loa...

Page 30: ...Orientation A Standard orientation Figure 36 Mounting Orientation B Upside down Figure 37 Mounting Orientation C Table top mounting Figure 38 Mounting Orientation D Horizontal CW Input on the Left Fi...

Page 31: ...des a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Installation and Maintenance of Solid state Control publication SGI 1 1...

Page 32: ...se articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation instructions manuals br...