DC Power Supply - 12V, 5 A,
60 W, Single-phase Input
Catalog Number 1606-XLB60BH
Reference Manual
Original Instructions
Page 1: ...DC Power Supply 12V 5 A 60 W Single phase Input Catalog Number 1606 XLB60BH Reference Manual Original Instructions ...
Page 2: ...Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Labels may also be on or inside the equipment to provide sp...
Page 3: ...ion Terminals 13 Lifetime Expectancy 13 Mean Time Between Failure 14 Electromagnetic Compatibility 14 Environment 16 Safety and Protection Features 17 Dielectric Strength 17 Approvals and Fulfilled Standards 18 Regulatory Compliance 18 Physical Dimensions and Weight 19 Series Operation 20 Operation on Two Phases 20 Use In a Tightly Sealed Enclosure 21 Prohibited Applications 21 DC Input 21 Chargin...
Page 4: ...4 Rockwell Automation Publication 1606 RM117A EN P July 2020 Notes ...
Page 5: ... value that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances usually 15 included For example DC 12V describes a 12V battery disregarding whether it is full 13 7V or flat 10V 230V AC A value with the unit V AC at the end is a momentary value without any additional tolerances included 50 Hz versus 60 Hz As long as not otherwise stated AC 100V and ...
Page 6: ...12 15V Factory setting 12V Output current 5 0 4 0 A Below 60 C 140 F ambient 3 8 3 0 A At 70 C 158 F ambient Derate linearly between 60 70 C 140 158 F Input voltage AC AC 100 240V 10 Mains frequency 50 60 Hz 6 Input current AC 1 0 A 0 6 A At 120 230V AC Power factor 0 55 0 47 At 120 230V AC Input inrush current 15 A peak 36 A peak At 120 230V AC 40 C 104 F cold start Efficiency 90 2 90 7 At 120 23...
Page 7: ...ker Attributes Values Notes AC 100V AC 120V AC 230V Input current Typ 1 15 A 1 0 A 0 60 A At 12V 5 A see Figure 4 Power factor Typ 0 58 0 55 0 47 At 12V 5 A see Figure 5 Start up delay Typ 50 ms 50 ms 60 ms See Figure 3 Rise time Typ 18 ms 18 ms 18 ms At 12V 5 A constant current load 0 mF load capacitance see Figure 3 Typ 30 ms 30 ms 30 ms At 12V 5 A constant current load 2 mF load capacitance see...
Page 8: ... 100V AC 120V AC 230V Inrush current Typ 12 Apeak 15 Apeak 36 Apeak At 40 C 104 F ambient cold start Typ 10 Apeak 12 Apeak 30 Apeak At 25 C 77 F ambient cold start Max 15 Apeak 18 Apeak 44 Apeak At 40 C 104 F ambient cold start Max 12 Apeak 15 Apeak 36 Apeak At 25 C 77 F ambient cold start Inrush energy Max 0 2 A2 s 0 3 A2 s 1 4 A2 s At 40 C 104 F ambient cold start Figure 6 Typical Turn on Behavi...
Page 9: ...and noise voltage Max 100 mVpp Bandwidth 20 Hz to 20 MHz 50 Ω Output current Nom 5 0 A At 12V and an ambient temperature below 60 C 140 F Nom 3 8 A At 12V and 70 C 158 F ambient temperature Nom 4 0 A At 15V and an ambient temperature below 60 C 140 F Nom 3 0 A At 15V and 70 C 158 F ambient temperature Overload behavior Continuous current Output voltage above 8V DC see Figure 10 Intermittent curren...
Page 10: ...OK lamp is also on during this time Attributes Values Notes AC 100V AC 120V AC 230V Hold up Time Typ 13 ms 23 ms 107 ms At 12V 5 A Typ 36 ms 55 ms 219 ms At 12V 2 5 A Min 10 5 ms 18 ms 85 ms At 12V 5 A Min 28 5 ms 43 ms 175 ms At 12V 2 5 A Figure 12 Hold up Time Versus Input Voltage Figure 13 Shut down Behavior Definitions 0 20 40 100 120 ms 90 120 155 190 230V AC Input Voltage Hold up Time 60 80 ...
Page 11: ... at 2 5 A 25 at 3 75 A 25 at 5 A Power losses Typ 0 2 W 0 2 W 0 3 W At no load Typ 3 6 W 3 4 W 3 4 W At 12V 2 5 A half load Typ 7 5 W 6 5 W 6 2 W At 12V 5 A full load Figure 14 Efficiency Versus Output Current at 12V Typ Figure 15 Losses Versus Output Current at 12V Typ Efficiency 0 86 88 90 85 91 5 A 1 3 4 Output Current 2 87 89 a 230V AC b 120V AC c 100V AC b c a Power Losses 0 0 7 5 W 5 A 1 3 4...
Page 12: ...r Output Filter VOUT Power Converter L N DC OK Status Indicato Figure 19 Front Side User Elements 1 Output terminals Dual terminals for the negative and positive pole Both poles are internally connected Positive output Negative return output 2 DC OK status indicator green The status indicator is on when the output voltage is above 9V 3 Output voltage adjustment potentiometer 4 Input terminals L Ph...
Page 13: ...ytic capacitors only states a maximum life of up to 15 years 131 400 h Any number that exceeds this value is a calculated theoretical lifetime which can be used to compare devices Attributes Descriptions apply to all terminals Type Push in termination Solid wire 2 5 mm2 max Stranded wire 2 5 mm2 max Stranded wire with ferrules 1 5 mm2 max American Wire Gauge AWG 24 12 Wire diameter max including f...
Page 14: ...and 2 this device must accept any interference received including interference that may cause undesired operation Do not use this device in an application where both of the following are true The device is used on AC 100V mains with more than 3 6 A load The application is sensitive to short output voltage dips during mains interruptions even with a length shorter than 20 ms Attributes Values in ki...
Page 15: ...00 4 5 L N 2 kV Criterion A N L Earthed output 4 kV Criterion A Surge voltage on output EN 61000 4 5 1 kV CriterionA Earthed 1 kV CriterionA Earthed 1 kV CriterionA Conducted disturbance EN 61000 4 6 0 15 80 MHz 10V Criterion A Mains voltage dips EN 61000 4 11 0 of 100V AC 0V AC 20 ms Criterion A C 40 of 100VAC 40V AC 200 ms Criterion C 70 of 100VAC 70V AC 500 ms Criterion A 0 of 120V AC 0V AC 20 ...
Page 16: ... overvoltage category III Input to PE According to IEC 60664 1 for altitudes up to 2000 m 6562 ft Degree of pollution 2 According to IEC 60664 1 non conductive Vibration sinusoidal 2 17 8 Hz 1 6 mm 0 063 in 17 8 500 Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 30 g 6 ms 20 g 11 ms 3 bumps direction 18 bumps intotal According to IEC 60068 2 27 Shock and vibration are tested in combination w...
Page 17: ...on between input and output measured with 500V DC Output overvoltage protection Typ 15 5V DC Max 16 0V DC If there is aninternal anomaly aredundant circuitlimitsthemaximumoutput voltage to 16V The outputshutsdown Toattempt a restart turntheinput power off for at least 90 s Class of protection II According to IEC 61140 Degree of ingress protection IP20 According to EN IEC 60529 Over temperature pro...
Page 18: ...US and Canada E File NMTR 7 E56639 NEC CLASS 2 planned UL Certificate NEC CLASS 2 Limited Power Source Listed in the UL 61010 2 201 approval report investigated according to UL 1310 Ind Cont Eq NEC CLASS 2 Regulation Names Regulation Symbols Notes CE EU Declaration of Conformity Trade conformity assessment for Europe The CE marking indicates conformance with the following European regulations RoHS...
Page 19: ...EN 50022 witha heightof7 5 mm 0 295 in or 15 mm 0 59 in Housing material High grade polycarbonate ABS blend material Installation clearances Keep the following min installation clearances 40 mm 1 57 in on the top 20 mm 0 79 in on the bottom 0 mm 0 in on the left side 0 mm 0 in on the right side If the adjacent device is a heat source increase the side clearances from 0 mm 0 in to 15 mm 0 59 in Pen...
Page 20: ...output terminals Keep an installation clearance of 15 mm 0 59 in left right between two power supplies and avoid installing the power supplies on top of each other Leakage current EMI inrush current and harmonics increase when using multiple devices Figure 25 Series Operation Operation on Two Phases The power supply can also be used on two phases of a three phase system Such a phase to phase conne...
Page 21: ...he enclosure Prohibited Applications Do not use the power supply in the following applications DC Input Do not operate this power supply with DC input voltage Charging of Batteries Do not use the power supply for the charging of batteries Parallel Use to Increase Output Power Do not parallel devices for higher output currents Parallel Use for 1 1 Redundancy This device is not recommended to build ...
Page 22: ...22 Rockwell Automation Publication 1606 RM117A EN P July 2020 Notes ...
Page 23: ...osures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application Installation and Maintenance of Solid State Control publication SGI 1 1 Designed to harmonize with NEMA Standards Publication No ICS 1 1 1987 and provides general guidelines for the application installat...
Page 24: ...cess Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation instructions manuals brochures and technical data publications rok auto literature Product Compatibility and Download Center PCDC Download firmware associated files such as AOP EDS and DTM and access product...