Chapter
5
Parameters and Programming
Overview of Parameters
This chapter describes both Display and Program parameters. Display parameters
are
read only
(they cannot be programmed), while Program parameters
can
be
changed to fit your motor control requirements. A Program Keypad Module,
Remote Keypad Module or CopyCat Keypad Module allow you to view or change
parameters. Communication Modules (RS1, DN1 or DN2) allow you to view or
change parameters with an additional device. A Ready/Fault Indicating Panel
cannot be used to view or change parameters. The table below describes which
parameters apply to the Preset Speed and Analog Signal Follower models
.
Some parameters pertain only to either the Analog Signal Follower or Preset Speed
model, not both.
Review the factory default settings. These parameters can be changed to meet your
specific application requirements with any of the following: Program Keypad
Module, Remote Keypad Module or CopyCat Keypad Module. The table below
provides a list of parameters that are frequently changed.
Commonly Changed Parameters
Table 5.A
Refer to the
Programming Example
on the next page for instructions.
Parameter Type
Analog Signal Follower Model
Parameter Numbers
Preset Speed Model
Parameter Numbers
Display
1 – 19
1 – 15, 17 – 19
Program
30 – 62, 65, 66, 69 – 76, 78 – 84
30 – 59, 61 – 73, 78 – 80
⇐
Indicates that parameter applies only to the Analog Signal Follower Model
⇐
Indicates that parameter applies only to the Preset Speed Model
Parameter
Setting
Default Setting
P30 - [Accel Time 1]
Desired accel time.
10.0 sec
P31 - [Decel Time 1]
Desired decel time.
10.0 sec
P33 - [Maximum Frequency]
Maximum frequency required.
60 Hz
P34 - [Stop Mode Select]
Desired stopping mode.
0
P35 - [Base Frequency]
Motor rated nameplate frequency.
60 Hz
P36 - [Base Voltage]
Motor rated nameplate voltage.
460V or 230V
P38 - [Boost Select]
Desired V/F boost setting.
2
P42 - [Motor Overload Current]
Motor nameplate Full Load Amps (FLA).
115%
P43 - [Current Limit]
Desired maximum output current.
150%
P46 - [Input Mode]
Desired control method.
0
P47 - [Output Configure]
Desired output relay function.
0
P56 - [Reset Functions]
Desired drive reset description.
0
P58 - [Internal Frequency]
Desired internal frequency.
60.0 Hz
P59 - [Frequency Select]
Desired frequency source.
0
P61 – P68 - [Preset Frequency 0-7]
Desired preset frequencies.
0-7
P74 – P76 - [Analog Input]
Desired analog input functionality.
0, 0.0, 100.0%
Summary of Contents for Allen-Bradley 160 SSC Series
Page 12: ...1 6 Getting Started End of Chapter ...
Page 58: ...5 20 Parameters and Programming End of Chapter ...
Page 66: ...A 4 Specifications End of Chapter ...
Page 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Page 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Page 82: ...C 6 CE Conformity End of Chapter ...
Page 87: ......