XM Dynamic Measurement Module Terminal Base
5
Publication
ICM-IN003D-EN-P - March 2013
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this
Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.
ATTENTION
This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING
This equipment must be mounted in an ATEX certified enclosure with a
minimum ingress protection rating of at least IP54 (as defined in IEC60529) and
used in an environment of not more than Pollution Degree 2 (as defined in IEC
60664-1) when applied in Zone 2 environments. The enclosure must utilize a
tool removable cover or door.
WARNING
This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
WARNING
This equipment must be used within its specified ratings defined by
Rockwell Automation.
WARNING
Provision must be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 140% of the rated voltage when applied
in Zone 2 environments.